两相电是串联关系,两电路串联,电流容量是两电路较小的一个,不能相加。两个100A breaker,串联仍然是100A。
-w4b(Watch for Beauty);
2014-9-25(#9008269@0)
100A的service,不过这里的入户线都是两相电,所以你的刀闸箱有right arm 和left arm,每个arm都可以有100A电流,总的来说,你可以有200A的电流,如果是200A的service,就可以总共有400A的电流。
-ding_ding(丁_丁);
2014-9-10(#8977227@0)
100A for each leg
if you're using appliance like AC/Stove/Dryer, they use both legs(2 pole, 240v), calculate current as, for example, 4000w / 240 = 16.7 amp, then each leg will be sucked 16.7 amp away by the appliance.
-wlh50111(小菜一碟);
2014-9-25(#9008233@0)
If you're using appliance like laptop, they use one leg only (1 pole, could be either), calculate current as, for example, 100w / 120 = 0.83amp, then the leg which the outlet is connected to is sucked away 0.83 amp current away,
-wlh50111(小菜一碟);
2014-9-25(#9008236@0)
the other leg won't be sucked.
Following this rule, you'll find out that 100 A service can support a lots of appliances especially your furnace and hot water tank goes with Gas.
-wlh50111(小菜一碟);
2014-9-25(#9008240@0)
if breaker break time to time, check your usage balancing of the two legs ( selected move 1pole breakers to another leg).
-wlh50111(小菜一碟);
2014-9-25(#9008241@0)