You say (炉子还在运作, 停不了了, after 温控器调到off 的位置) is it only the Fan non stop working? Or the furnace/gas burning all working?
If the furnace problem is controller relate, 温控器调到off 的位置 can not prove the problem, you may want to test the funrace "CPU Controller" and ,
1: Power off the furnace completly, there is a switch in the furnace area,.
2: wait for 1 minute. check if the fan stopped.
3: Fan should stop after power is switched off.
4: After 1 minutes switch it back on,
5: If the fan running again after switched back on.
6: It mean the relay or the control circuit is "STUCK CLOSE"
PM me if you like, I can explain to you on phone. I am not a technician, but I look after my own home and my friend home for long time. Understand how it work and how to trouble shooting