Do you feel comfortable open up the furnace side panle?

本文发表在 rolia.net 枫下论坛1st of all. Set the thermostat at a higher setting, found the furnace shut off switch in the area power it OFF then back ON, and wait for a fan to start, after the "purge" fan starts count for 10 to 15 seconds, Observe the igniter to turn on(Bright Red Hot), you may or may not see it, but it is ok, if should come on within the 20 seconds after the “purge”, if no any other action beside the fan turned on after 1 minutes. This is what you need to do.
Do you feel comfortable open up the furnace side panel?
Open it up if you are comfortable, (remove ONLY the "main furnace door", not the blower door.) locate the "CPU" which a white box or a control circuit broad. Visually search a blinking Red LED, most furnace use the blink LED as a self-diagnostic indicator, which tells you what is wrong and what is not working. If you see it blink 3 times. It means the "pressure switch not confirmed"

Where is the pressure switch????? Inside the unit, with the panel opened locate the pressure switch, it look like a "Hockey puck" have two wires and a rubber tub connected to it...use your finger or a small screw drive “ Tap” on it slightly while the fan is running... come back and tell me what you see after you done all this.更多精彩文章及讨论,请光临枫下论坛 rolia.net
Report

Replies, comments and Discussions:

  • 枫下家园 / 美丽家居 / 家里的暖气系统昨天不能正常工作了,开关设在自动的时候 设的温度高于室内温度也不工作.开关设在ON的时候,又只有 冷风打上来,没有热风.好像是暖气点不着火了,有没有知道 怎么弄的?先谢了....
    • 查查是不是点火器坏啦。
    • 我遇到同样问题,叫修暖气的人来看,糊弄我说是马达旧了,要换。我没让他修。打开暖炉盖子,反复试验并观察,发现冷凝水管堵了。现在我每年开暖气前,都检查冷凝水管
      • 冷凝水管怎么打开?我的炉子是比较新的电子的.....
        • 拔下来
    • I would check the following..
      Have you look at the furnace controller "CPU" ? Some people call it computer. for me it is just a timing device monitors all safety switch and controls the gas valve to fire at the correct timing to heat up the house
      There is a Self Diagnost LED indicator on the CPU. If fan running ok, Locate the "Red LED" on the CPU PCB, if it steady "ON" mean control circuit is ok,
      if the LED is Flashs, count how many time,3 flashed=pressure switch not confirmed. 4 flashed =over heat, 5 flashe = some other switch is open,,,,,,,,,,if not Flashing LED it may be the inigtor not working,,,,,,
      • CPU在哪里看,也是在地下室打开FURNACE的盖子看的吗?
        • tell me make and modle of the furance, I may have more information for you.
          • the modle of furnace it's carries weather maker 9200 ultra high efficiency gas furnace, please tell me more, thanks!
            • Do you feel comfortable open up the furnace side panle?
              本文发表在 rolia.net 枫下论坛1st of all. Set the thermostat at a higher setting, found the furnace shut off switch in the area power it OFF then back ON, and wait for a fan to start, after the "purge" fan starts count for 10 to 15 seconds, Observe the igniter to turn on(Bright Red Hot), you may or may not see it, but it is ok, if should come on within the 20 seconds after the “purge”, if no any other action beside the fan turned on after 1 minutes. This is what you need to do.
              Do you feel comfortable open up the furnace side panel?
              Open it up if you are comfortable, (remove ONLY the "main furnace door", not the blower door.) locate the "CPU" which a white box or a control circuit broad. Visually search a blinking Red LED, most furnace use the blink LED as a self-diagnostic indicator, which tells you what is wrong and what is not working. If you see it blink 3 times. It means the "pressure switch not confirmed"

              Where is the pressure switch????? Inside the unit, with the panel opened locate the pressure switch, it look like a "Hockey puck" have two wires and a rubber tub connected to it...use your finger or a small screw drive “ Tap” on it slightly while the fan is running... come back and tell me what you see after you done all this.更多精彩文章及讨论,请光临枫下论坛 rolia.net
              • 谢谢,你的详细指示,我找了个师傅修了后来, 是点火的那个黑色的硅片烧断了,重新换个 硅片就好了....